SBI-card-Chennai

The SBI Card Chennai office at KRC Commerzone features efficient LED lighting with lux levels within recommended standards, low indoor noise levels, and a well-maintained centralized HVAC system, though AHU filter cleaning is advised. Voltage unbalance was minimal at 0.5%, but current harmonics (38%) exceeded limits, prompting mitigation recommendations. The UPS system was underloaded with a low power factor, requiring optimization. Plumbing fixtures are functional, and water quality is within acceptable limits, with daily consumption averaging 8,000 litres. Suggested improvements include HVAC maintenance, harmonics control, UPS optimization, and IoT-based energy monitoring to boost efficiency and sustainability.