The SBI Cards Gurugram office demonstrates strong sustainability measures with efficient LED lighting, adequate lux levels in most areas, and well-maintained AHUs ensuring thermal comfort. Indoor noise levels are generally within recommended standards, and plumbing fixtures are functional with TDS values meeting BIS requirements. Voltage unbalance was minimal (<1%), though high current harmonics in some panels call for corrective filtering. Recommended actions include installing an IoT-based energy monitoring system, upgrading to dual-flush water closets and low-flow taps to save 36% water, and enhancing harmonic control for improved reliability and efficiency.